Tripp Lite series SmartOnline 5000VA 4500W 208V Online Double-Conversion UPS - L6-30P, 2 L6-20R, 2 L6-30R, Hardwired Output, Network Card, Extended Run, 3U Rack/Tower
| Product Name |
Eaton Tripp Lite series SmartOnline UPS
|
| Catalog Number |
SU5000RT
|
| Product Length/Depth |
25.04 in
|
| Product Height |
5.12 in
|
| Product Width |
17.32 in
|
| Product Weight |
114.02 lb
|
| Compliances |
FCC Compliant
CE Marked RoHS FCC Class A ENERGY STAR certified REACH |
| Certifications |
NOM
IEC/EN 62040-2 CSA 22.2 UL 1778 cTUVus |
| Topology |
Online/Double-conversion
|
| Rack size |
3U
|
| Color |
Black
|
| VA rating |
5000 VA
|
| Wattage |
4500 W
|
| Rack mounting kit |
Yes
|
| Package contents |
|
| Surge protection |
Yes
|
| Internal bypass |
Yes
|
| Current Crest Ratio |
3:1
|
| Input connection |
Hardwire; L6-30P
|
| Input cord length |
10 ft
|
| Input nominal voltage |
200 VAC/208 VAC/220 VAC/230 VAC/240 VAC
|
| Nominal frequency |
50/60 Hz
|
| Input frequency range |
50/60 Hz
|
| Input power factor |
>0.99 typical
|
| Receptacle |
(2) L6-20R; (2) L6-30R; Hardwire
|
| Number of Outputs L6-20R |
2
|
| Number of Outputs L6-30R |
2
|
| Number of outputs hardwired |
1
|
| Output waveform |
True sine wave
|
| Voltage |
208 V
|
| Output nominal voltage |
208V default (200/208/220/230/240V)
|
| Runtime graph |
|
| Battery replacement |
EBP-1803
|
| Battery type |
Valve Regulated Lead Acid (VRLA)
|
| Extended battery capability |
Add up to 4 extended battery modules (EBM). Part number BP180RT
|
| Standard factory warranty |
|
| Extended service plans |
|
| Runtime at half load |
11 min
|
| Ethernet interface |
Yes
|
| Includes network card |
Yes
|
| Software compatibility |
PowerAlert
|
| Altitude |
<1000m for nominal power, 10% power degrading every 1000m (up to 3000m)
|
| Noise level |
<45 dB at 1 meter
|
| Relative humidity |
0-95% non-condensing
|
| Front Panel LCD Display |
LCD graphical display
|
| Input Plug Type |
NEMA L6-30P
Hard-wire |
| Output Receptacles |
L6-30R
L6-20R Hardwire |
| Product Features |
Emergency Power Off (EPO)/Remote On-Off (ROO)
Expandable Runtime L6-30P 10ft. |
| Product Highlights |
Protects equipment against blackouts, brownouts, transient surges and line noise
Menu-driven LCD interface keeps you updated on critical load information in real time Optional extended battery modules allow extended runtime to keep equipment powered Keeps equipment running during outages to allow time for file saves and safe shutdown Pre-installed WEBCARDLXE network card enables full remote access and control |
| PowerAlert Software |
For local monitoring via the UPS’s built-in communication ports, download PowerAlert software at https://tripplite.eaton.com/products/power-alert
|
| Network Management Cards |
WEBCARDLXE
|
| Network Management Cards Details |
Network management card included
|
| Efficiency at max. load |
93%
|
| Input voltage range |
200-240V
|
| Max number of battery packs |
4
|
| Output frequency |
50/60 Hz
|
| Output power factor |
0.9
|
| Phase (input) |
Single-phase
|
| Runtime at full load |
3 min. (4500W)
|
| Communication interface |
USB and DB9 serial cables included
USB Contact closure RS-232 Included network card |
| Battery Access |
Battery access door
|
| Typical Battery Runtime |
Expandable Runtime
|
| Dc Voltage |
180
|
| Operating Temperature Range |
32° to 104°F (0° to 40°C)
|
| Communications Cable |
USB and DB9 serial cables included
|
| Input Circuit Breakers |
Recommended 30A upstream
|
| Optional Mounting Accessory Notes |
2 post rail kit available, part # RK2PC
|
| Output Circuit Breakers |
20A breaker protects L6-20R outlets
|
| High Voltage Transfer to Battery Power |
276V
|
| Low Voltage Transfer to Battery Power |
176V
|
| Application |
Mission Critical Applications
|
| Switch configuration |
RPO / ROO
|
| AC suppression joule rating |
390
|
| Housing material |
Metal
|
| Output AC waveform (AC mode) |
Pure Sine wave
|
| Output AC waveform (battery mode) |
Pure sine wave
|
| Output Capacity (kVA) |
5
|
| Operating Elevation |
<1,000 meters for nominal power; 10% power derating every 1000 meters (up to 3000 meters) at 40°C
|
| AC Suppression Response Time |
0 ms
|
| Alarm Interface |
Press ESC to silence the alarm
|
| Audible Alarms |
Audible alarm indicates utility failure, low-battery, overload, other UPS/Battery fault or remote shutdown conditions
|
| Battery Start Capability |
Cold-start operation supported
|
| Cooling Method |
Fan
|
| Battery Replacement Description |
Hot-swappable, user replaceable batteries. UPS requires 1 Replacement Battery Cartridge.
|
| LED Indicators |
4 status-indicating LEDs
|
| Frequency Rating Details |
50 or 60Hz, autosensing or configurable as a frequency converter
|
| Minimum Required Rack Depth With External Battery Pack |
31
|
| Output Voltage Regulation (Line Mode) |
+/- 1%
|
| Output Voltage Regulation(Battery Mode) |
+/- 1%
|
| Recommended Electrical Service |
30A
|
| Storage Temperature |
With battery: 32° to 104°F (0° to 40°C); without battery: -13° to 131°F (-25° to 55°C)
|
| Included Mounting Accessory Description |
Includes 4 post rackmount and tower pedestal accessories
|
| Input Nominal Voltage Description |
Factory configured to 208V
|
| Network Monitoring Port Description |
WEBCARDLXE Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications; not compatible with WEBCARDLX
|
| Nominal Voltage Details |
200V, 208V, 220V, 230V, 240V
|
| Voltage Regulation Description |
Online, double-conversion power conditioning
|
| Plug Type |
NEMA L6-30P
|
| Maximum Input Amps |
23
|
| Minimum Required Rack Depth (cm) |
78.74
|
| Minimum Required Rack Depth (inches) |
31
|
| Total Harmonic Distortion |
< 2% THDV on linear load; < 5% THDV on non-linear load
|
| UPS Input Cord Length (m) |
3.1
|
| Power Mode Transfer Time |
0 ms
|
| Optional Accessories |
2 post rackmount (RK2PC)
|
| EMI AC Noise Suppression |
EMI / RFI AC Noise Suppression
|
| UPS Input Connection Type |
Hardwire
L6-30P |
| External Battery Pack Compatibility |
BP180RT
|
| Green Energy-Saving Features |
High efficiency economy mode operation
|
| High Availability UPS Features |
Automatic voltage regulation (AVR)
Hot swappable batteries On-Line/Double-Conversion Remote management Expandable battery backup Pure sine wave output Zero transfer time Surge/noise protection |